This is in the liquid line of the outdoor coil.
It begins the defrosting cycle after a period of 30, 60 or 90
minutes (as selected) has elapsed from the start-up or since
the previous defrosting, when the temperature detected
drops to -5°C or less.
It stops the defrost cycle when the liquid temperature reaches
13°C or stays at a minimum of 7°C for at least 5 minutes.
It prevents defrost in mild climates when it does not detect a
sufficiently low temperature.
The reading for the beginning of defrost of 30, 60 or 90
minutes is nominal. These periods are based on an outside
temperature of 2°C, a highly unfavourable level which
causes considerable frost formation.
At lower temperatures the overall humidity content of the
ambient air is lower, making it possible to postpone the
defrost cycles, thus saving energy. For example, at -10°C
outside temperature, the reading times for the beginning of
defrost will be 60, 90 & 120 minutes.
Balance point
It prevents functioning of the support system when the outside
temperature is higher than the balance point as adjusted on
the plaque. In this way, we save the heater's functioning as
long as the heat pump is capable of satisfying the building's
requirements. The balance point can be adjusted between
14°C and -4°C. This avoids the necessity of fitting an additional
outside thermostat.