6.2 Measure 2: Type I Exhaust Hood Airflow Limitations
6.2.1 Code Language SECTION 144 – PRESCRIPTIVE REQUIREMENTS FOR SPACE CONDITIONING SYSTEMS (o) Type I Exhaust Hood Airflow Limitations. For kitchen/dining facilities having total Type 1 and Type II kitchen hood exhaust airflow rates greater than 5,000 cfm, each Type 1 hood shall have an exhaust rate that complies with Table 1. If a single hood, or hood section, is installed over appliances with different duty ratings, then the maximum allowable flow rate for the hood or hood section shall not exceed the Table 1 values for the highest appliance duty rating under the hood or hood section. Refer to the ASHRAE Standard 154 for definitions of hood type, appliance duty, and net exhaust flow rate