fredag 10 april 2015
TESTING METHODS AND EQUIPMENT
TESTING METHODS
AND EQUIPMENT
There are two main methods of testing.
The pressurization subtraction method utilizes
a pressurization unit (i.e. a high-powered fan
set up in a doorway and connected to
pressure gauges) to pressurize first the
entire space that is heated and/or cooled
and then the same space with the duct
system blocked off. This method is less
accurate than the duct testing method.
The duct testing method uses a calibrated
fan that gently pressurizes the ducts and
measures the airflow through the ducts to
indicate total leakage. The duct tester
consists of a portable fan with calibrated
digital pressure gauges that is connected at
the blower compartment of the air handler,
or attached to the main return grill. All of
the duct registers and grills are temporarily
sealed, and the duct tester fan is turned on
to pressurize the system. The fan pressure
is read from the gauges and converted to an
equivalent duct leakage rate in cubic feet per
minute (cfm). If the amount of air loss falls
outside acceptable limits, sealing will be
required to correct the condition. This
method of testing is preferred, because
it measures low airflow accurately, and
simulates what takes place under normal
operating conditions.
Prenumerera på:
Kommentarer till inlägget (Atom)
Inga kommentarer:
Skicka en kommentar